Product details & specifications
What this product does
A time-delay RCD provides residual-current protection with a deliberate operating delay. In a coordinated arrangement, this gives a downstream device an opportunity to clear a fault first.
When to use it
Use it where the design specifies selective residual-current protection, commonly upstream of other RCD-protected circuits. Correct coordination can reduce the extent of a disconnection.
What is included
- One WARTD263-100: 63A, two-pole Type A time-delay RCD with 100mA sensitivity.
Choosing your options
Match the current-carrying rating, pole count, time-delay characteristics and downstream devices. The amp rating is not the residual trip threshold: 100mA describes residual-current sensitivity.
What it does not replace
This 100mA time-delay RCD is not a replacement for required 30mA additional protection. It does not trip for overload or short circuit, so it requires appropriately coordinated overcurrent protection.
Specifications and dimensions
Use the selected configuration above for its part code and current price. Match the exact device and enclosure to the manufacturer’s technical information, allowing cable-entry and wiring clearance as well as the product dimensions.
Manufacturer range and technical information
Common questions
Which device should clear a downstream fault first?
The purpose of selectivity is to let the appropriate downstream protective device operate before the upstream time-delay device, where their characteristics and the fault allow.
Is time delay just a cure for nuisance tripping?
No. It is a designed protection and coordination feature. Diagnose unwanted tripping instead of changing sensitivity or delay without checking the circuit design.