Type B RCDs provide protection against residual fault currents / earth leakage in AC supply applications with specific waveform characteristics.
Type B RCDs are used where smooth and/or pulsating DC residual currents can occur, non-sinusoidal waveforms are present or frequencies greater that 50Hz; for example, Electric Vehicle Charging, certain 1-phase devices, micro generation or SSEGs (Small Scale Electricity Generators) such as solar panels and wind generators.
Key Features
DIN rail mounted
2-Pole / Single Phase
RCD Type: B
Tripping Sensitivity: 30mA
Current rating: 63A
Voltage rating: 230V AC
Short-circuit current capacity: 10kA
IP20 (needs to be in suitable enclosure for outdoor use)
In accordance with IEC/EN 62423 & IEC/EN 61008-1
Dimensions
54mm x 79mm x 91mm
DIN 2 module width
RCD Selection
B Type Tripping is ensured for sinusoidal AC residual currents, alternating residual currents up to 1000Hz, pulsating DC residual currents and for smooth DC residual currents (such as those DC leakage from EVs of >6mA); whether applied suddenly or increasing slowly.
Safe use A suitably rated RCBO/MCB device must also be used to provide the correct level of over current protection whilst avoiding unnecessary tripping.
Users of this product assume responsibility for the correct design and installation of their EVSE. Consult theEcoharmonywebsite or an electrical contractor if needed.Ecoharmony will not be held liable for injury to living creatures nor damage to property arising from incorrect use of this product.